Siemens alternator 6 cylinders 100 KW natural gas generator 3 phase with factory price
√ 100 KW Natural Gas Generator Set's More Details
-------------------------Requirements For Natural Gas
Within 1m from pressure regulating valve of gas intake
Δ The ratio of CH4 in natural gas ≥70%
Δ Pressure of natural gas: 80-200kpa, rate of pressure change ≤ 1kpa/min
Δ H2S ≤ 20mg/Nm3
Δ Impurity particle size ≤ 5μm, impurity content ≤ 30mg/Nm3
Δ Moisture content ≤ 40g/Nm3
--------------------------Application Place
Δ Oil field
Δ Industrial Zone
Δ Petroleum chemical plant
Δ Used as standby power souce instead of natural gas generating
Δ Supply power for the auxiliary engine which work in oil well
------------------------ Company Profile
Δ Established in 2008
Δ Factory area over 40000 square meters
Δ Over 260 employees, technicians over 100 people
Δ Provide repaire service free during the guarantee period
Δ Got the CE, ISO14001, ISO9001 certification
Δ Established cooperation relationship with brands
Δ Website lvhuanpower.en.made-in-china.com
------------------------Our Advantages
Δ Strong structure & Strengthen accessories
Δ Easy Start & ATS system
Δ Auto voltage regulation & Stable working condition
Δ Imported and easy-operation control system
Δ Imported and accurate gas control system
Δ Standard parts for easy maintain
Δ long life operation and low-operation cost
Notice About Power Plant Construction ! ! ! ! ! ! ! ! ! ! ! ! !
× Generator Room is usually constructed in open or semi-open type. The floor should be easily to clean and not easily to spark.
× If you want to construct Closed Generator Room, you must construct a single storey building. The open direction of all the doors and windows must turn outside. Please install some big capacity displacement device to avoid gas gathering.
× Generator Room and the Operation Room must be separated, can not be directly connected. The observation window should be with double deck glass protected by steel wire mesh.
× Lightning arrester is necessary.
× Prepar enough fire extinguishing appliances.
× "NO FIRE" mark should be obvious, open flame in the generator room is not allowed.
× In the exhaust gas, there are combustible gas. So, the exhaust pipe of the generator must be leaded to outside of room. The exhaust pipe must be connected tightly.